250+ TOP MCQs on Electric Field and Potential of a Long Straight Conductor – 1 and Answers

Power Systems Multiple Choice Questions on “Electric Field and Potential of a Long Straight Conductor – 1”.

1. Shunt admittance of a transmission line comprises of ______
A. capacitance with conductance
B. capacitance with inductance
C. resistance with inductance
D. capacitance with susceptance

Answer: A
Clarification: Shunt admittance is capacitance with conductance in the branch.

2. Conductance is the result of the leakage over the surface of insulators.
A. True
B. False

Answer: A
Clarification: Conductance comes into the picture due to the leakage current over the conductor’s surface.

3. Charging current in the transmission line is _______________
A. drawn at open as well as closed end of the transmission line
B. drawn at closed end of the transmission line
C. drawn at open end of the transmission line
D. drawn at the shunt capacitance at closed end of transmission line.

Answer: A
Clarification: Charging current in transmission line is drawn even when the far end of the TL is open.

4. A three phase 50 Hz transmission line has flat horizontal spacing with 3.5 m between adjacent conductors. The conductors are No. 2/0 hard drawn copper (outside diameter = 1.05cm). The voltage f the line is 110 kV. The capacitance to neutral per kilometre of line is
A. 0.00826 μF/km
B. 0.0826 μF/km
C. 0.01652 μF/km
D. 0.1652 μF/km

Answer: A

5. A three phase 50 Hz transmission line has flat horizontal spacing with 3.5 m between adjacent conductors. The conductors are No. 2/0 hard drawn copper (outside diameter = 1.05cm). The voltage f the line is 110 kV. The capacitive reactance to neutral per kilometre of line is ____________
A. 0.384 x 106 Ω/km to neutral
B. 0.768 x 106 Ω/km to neutral
C. 0.284 x 106 Ω/km to neutral
D. 0.642 x 106 Ω/km to neutral

Answer: A

6. A three phase 50 Hz transmission line has flat horizontal spacing with 3.5 m between adjacent conductors. The conductors are No. 2/0 hard drawn copper (outside diameter = 1.05cm). The voltage f the line is 110 kV. The line charging current per km of the line is _______________
A. 0.17 A/km
B. 0.34 A/km
C. 0.24 A/km
D. 0.48 A/km

Answer: A

7. A three phase 50 Hz transmission line has flat horizontal spacing with 3.5 m between adjacent conductors. The conductors are No. 2/0 hard drawn copper (outside diameter = 1.05cm). The voltage f the line is 110 kV. The line charging current per conductor of the line is _____________
A. 0.085 A/km
B. 0.17 A/km
C. 0.12 A/km
D. 0.24 A/km

Answer: A

8. A three phase 50 Hz transmission line has flat horizontal spacing with 3.5 m between adjacent conductors. The conductors are No. 2/0 hard drawn copper (outside diameter = 1.05cm). The voltage f the line is 110 kV. The reactive volt amperes generated by the line is
A. 31.4 kVAR
B. 62.8 kVAR
C. 42 kVAR
D. 56 kVAR

Answer: A